Construction calculators

Wire Size Calculator

Updated Nov 12, 2026 By Infinity Calculator Formulas Sources
Rate
Determines the voltage drop formula used.
Copper has lower resistance; aluminum is lighter & cheaper.
Affects ampacity rating of the conductor.
Free air allows higher ampacity ratings.
Enter a valid voltage
For loads running ≥ 3 hours. Multiplies current by 1.25 for sizing.
Enter a valid current
One-way distance — the calculator accounts for full round-trip internally.
Enter a valid distance
NEC recommends ≤ 3% for branch circuits, ≤ 5% total (feeder + branch).
Enter a valid percentage (0.1-25)

Recommended Wire Size

Recommended Gauge
—
Wire Size (mm²)
—
Actual Voltage Drop
—
Voltage Drop %
—
Voltage at Load
—
Ampacity (Derated)
—
Power Loss (Watts)
—
Wire Needed (Total)
—
Voltage Drop Visualization
0%
0%1%2%3%5%7%10%+
Copper vs. Aluminum Comparison
Copper
Recommended Gauge—
Voltage Drop—
Ampacity—
Power Loss—
Approx. Weight—
Aluminum
Recommended Gauge—
Voltage Drop—
Ampacity—
Power Loss—
Approx. Weight—
Voltage Drop by Wire Gauge
Voltage Drop vs. Distance
All Wire Gauges — Detailed Breakdown
AWG mm² Ω/1000ft Ampacity Derated Amp. V-Drop (V) V-Drop (%) Power Loss (W) Status

Introduction

Choosing the right wire size is one of the most important steps in any electrical project. If you use wire that is too small, it can overheat and cause a fire. If you use wire that is too big, you waste money. This wire size calculator helps you find the correct wire gauge for your project based on key factors like the length of the wire run, the current (amps) the circuit will carry, and the voltage of your system. It also accounts for acceptable voltage drop so your lights, motors, and other devices work the way they should. This tool helps you pick the right wire for wiring a new home, running power to a shed, or setting up a circuit in a commercial building. Just enter your project details, and the calculator will recommend the proper American Wire Gauge (AWG) size for a safe and efficient installation.

How to Use Our Wire Size Calculator

Enter a few details about your electrical setup below, and this calculator will tell you the right wire size (gauge) you need for your project.

Voltage: Enter the voltage of your electrical system. Common values are 120V or 240V for homes, and 208V or 480V for commercial buildings.15

Single Phase or Three Phase: Pick the phase type of your circuit. Most homes use single phase.15 Larger buildings and heavy equipment often use three phase.

Amperage (Amps): Enter the total amps your circuit needs to carry. You can find this on the nameplate of your equipment or breaker.

One-Way Wire Length (Feet): Enter the distance in feet from your electrical panel to the device or load. Measure just one way, not the round trip.

Acceptable Voltage Drop (%): Enter the maximum voltage drop you will allow. An informational note in the National Electrical Code (NEC) uses 3% for branch circuits and 5% in total for feeder and branch circuits.4

Conductor Material: Choose copper or aluminum. Copper carries more current in a smaller size but costs more. Aluminum is lighter and cheaper but requires a larger gauge.

Continuous Load: Check this box if the full current will run for 3 hours or more. The calculator then sizes the wire's ampacity for 125% of your current, while voltage drop and power loss use the current you entered (times any extra safety factor).

Equipment Terminals: In the Advanced Settings, the standard choice limits the wire to its 60°C ampacity on circuits up to 100 A or on wire of 1 AWG and smaller, and to its 75°C ampacity otherwise. Choose a higher rating only when the breaker, panel or device is listed for 75°C or 90°C wire.

What Is Wire Size and Why Does It Matter?

Wire size refers to the thickness of an electrical conductor, measured in AWG (American Wire Gauge) in the United States. Picking the right wire size is one of the most important steps in any electrical project. If the wire is too small, it can overheat, waste energy, or even start a fire. If the wire is too big, you spend more money than you need to. The goal is to find a wire that can safely carry your electrical load over the required distance without losing too much voltage along the way.

How Wire Gauge Numbers Work

AWG uses a numbering system that can seem backwards at first. Smaller numbers mean thicker wire. For example, 14 AWG is a thin wire used for light-duty circuits like bedroom outlets, while 4/0 AWG is a very thick cable used for heavy-duty applications like main service panels. The code limits 14 AWG copper to a 15 amp breaker or fuse.9 4/0 AWG copper is rated 195 to 260 amps depending on its insulation.10 Once you go past 4/0, wire sizes are given by cross-sectional area in kcmil (thousands of circular mils).2 Common sizes are 250, 300, and 500 kcmil. The NEC ampacity tables list sizes from 250 up to 2000 kcmil.10 Every three steps in AWG number roughly doubles or halves the cross-sectional area of the conductor.1

Understanding Voltage Drop

Every wire has some resistance, and that resistance causes a loss of voltage as electricity travels through it. This loss is called voltage drop. The longer the wire run and the more current it carries, the greater the voltage drop.14 An informational note in the National Electrical Code (NEC) says branch circuits sized to keep voltage drop at or below 3% at the farthest outlet, with 5% total on the feeder and branch circuit, provide reasonable efficiency of operation.4 Too much voltage drop can cause lights to dim, motors to run hot, and equipment to malfunction, and a detailed analysis of voltage loss on a specific circuit is available from our dedicated Voltage Drop Calculator.

Key Factors That Determine Wire Size

  • Current (Amps): The amount of electrical current the circuit must carry. Higher current needs thicker wire.
  • Distance: Longer wire runs create more resistance, which increases voltage drop. On long runs, voltage drop often calls for a larger wire than ampacity alone would.
  • Voltage: Lower-voltage systems (like 12V DC) are much more sensitive to voltage drop than higher-voltage systems (like 240V AC). At the same power, a 12V circuit also carries 20 times the current of a 240V circuit, so on the same wire its percentage drop is 400 times larger. This is why low-voltage landscape lighting and solar installations often require surprisingly large wire.
  • System Type: Single-phase AC and DC circuits use the same voltage drop formula, with a factor of 2 for the wire out to the load and back. Three-phase systems use a factor of √3 (about 1.73) in place of 2.14 For the same current on the same wire, that gives about 13% less voltage drop. These formulas use the wire's resistance alone, as for DC or an AC load at a power factor of 1.0. On AC circuits at a lower power factor, large wires see more drop than this: at a power factor of 0.85, 500 kcmil copper in PVC conduit has an effective impedance of 0.043 ohms per thousand feet, against an AC resistance of 0.027.16
  • Conductor Material: Common aluminum conductor wire conducts 61% as well as copper.2 That gives copper about 39% less resistance for the same size, so it can carry more current in a smaller size. Aluminum is lighter and cheaper but requires a larger gauge for the same job.
  • Insulation Temperature Rating: Wire insulation rated for higher temperatures (like THHN at 90°C) allows the conductor to carry more current than insulation rated for lower temperatures (like TW at 60°C).5 The equipment at each end of the wire can limit this. Unless the equipment is listed for wire with a higher rating, circuits of 100 A or less and terminals marked for 14 AWG through 1 AWG wire use the wire's 60°C ampacity, while circuits over 100 A and terminals marked for wire larger than 1 AWG use its 75°C ampacity.13 Wire with a higher rating can still use that rating when its ampacity is corrected for heat or reduced for bundling.13

Ampacity and Derating

Ampacity is the current a conductor can carry continuously under its conditions of use without going over its temperature rating.3 The NEC publishes ampacity tables based on conductor size, material, insulation type, and installation method.10 However, real-world conditions often reduce a wire's ampacity through a process called derating:

  • Ambient temperature: The NEC ampacity tables assume 30°C (86°F) surrounding air.6 Ampacities are corrected downward for hotter air and upward for cooler air.6 In hot air, the wire cannot shed heat as easily.
  • Conduit fill: When more than three current-carrying conductors share a conduit or cable, or when cables outside a conduit run together without spacing for more than 24 inches (600 mm), heat builds up and the ampacity of each conductor is reduced.6 For example, 4 to 6 conductors in a conduit derate ampacity to 80%.7 The correct conduit size depends on the number and type of wires you need to pull, which our Conduit Fill Calculator can determine.
  • Continuous loads: A continuous load is one whose maximum current runs for 3 hours or more.8 The NEC requires branch-circuit conductors to carry at least the noncontinuous load plus 125% of the continuous load.4 This provides a built-in safety margin.
  • Small wires: In general, after these corrections, the breaker or fuse on 14, 12 and 10 AWG copper may not exceed 15, 20 and 30 amps, and on 12 and 10 AWG aluminum, 15 and 25 amps.9

Copper vs. Aluminum

Copper is the most common choice for residential and commercial wiring because it conducts electricity better, is easier to work with, and fits in smaller spaces. Aluminum costs less and weighs about one-third as much, making it a popular choice for larger feeder cables and utility service entrances. Aluminum wire is used for distribution lines, building wire and power cable.2 When using aluminum, you typically need to go one or two wire sizes larger than you would with copper to achieve the same performance. Aluminum also requires special connectors rated for aluminum to prevent corrosion and loose connections. Connections to aluminum wire can deteriorate over time and overheat.17 On the 10 and 12 AWG aluminum branch circuits in some older homes, the lasting repairs are replacing the wire with copper or joining short copper pigtails with connectors made for that repair. Switches and outlets marked CO/ALR are at best an incomplete repair.17

Practical Tips

Always measure the one-way distance from the panel to the load. The calculator accounts for the full round-trip length of the circuit internally. When in doubt, it is always safer to go one size larger than the minimum. A slightly oversized wire costs a little more upfront but reduces energy waste, runs cooler, and gives you room to add load in the future. For any project involving electrical wiring, check your local building codes and consult a licensed electrician to make sure your installation is safe and legal.


Formulas used

Voltage Drop (Single-Phase / DC) 14
V_{drop} = 2 \times (I_{load} \times SF) \times R \times L
Voltage Drop (Three-Phase AC) 14
V_{drop} = \sqrt{3} \times (I_{load} \times SF) \times R \times L
Voltage Drop Percentage
V_{drop\%} = \frac{V_{drop}}{V_{source}} \times 100
Design Current (with NEC 125% and Safety Factor)
I_{design} = I_{load} \times C_{cont} \times SF \quad \text{where } C_{cont} = \begin{cases} 1.25 & \text{continuous} \\ 1.0 & \text{otherwise} \end{cases}
Power Loss in Conductors
P_{loss} = (I_{load} \times SF)^{2} \times \frac{R_{1000}}{1000} \times L \times n \quad \text{where } n = \begin{cases} 2 & 1\phi / DC \\ 3 & 3\phi \end{cases}
Temperature Derating Factor (NEC 310.15) 6
f_{temp} = \sqrt{\frac{T_{rated} - T_{ambient}}{T_{rated} - 30}}
Derated Ampacity
A_{derated} = \min(A_{base} \times f_{temp} \times f_{fill},\ A_{term},\ A_{240.4(D)})

Frequently asked questions

What wire size do I need for a 30 amp circuit?

For a 30 amp circuit using copper wire, you typically need 10 AWG wire for short runs. The code allows overcurrent protection of up to 30 amperes on 10 AWG copper.9 Over a long run, voltage drop can call for a larger wire. Stranded 10 AWG copper has a resistance of 1.24 ohms per thousand feet at 75°C.12 At 30 amps over a 100 foot run, that is a drop of about 7.4 volts, or 3.1% of 240 volts. On a 240 volt circuit, 10 AWG stays within 3% up to about 97 feet and 8 AWG up to about 154 feet. On a 120 volt circuit, those limits are about 48 feet and 77 feet. Enter your exact distance and voltage in the calculator to get a precise answer.

What does AWG mean?

AWG stands for American Wire Gauge. It is the standard system used in the United States to measure wire thickness. The smaller the AWG number, the thicker the wire.1 For example, 10 AWG is thicker than 14 AWG.

What is the NEC 125% rule for continuous loads?

A continuous load is one whose maximum current runs for 3 hours or more.8 The National Electrical Code requires the wire to carry at least the noncontinuous load plus 125% of the continuous load.4 Check the "Continuous load" box in the calculator, and it will multiply your current by 1.25 when it checks ampacity.

What is the difference between single-phase and three-phase?

Single-phase power is what most homes use. A typical home service has two hot wires and a neutral, with 120 volts from either hot wire to the neutral and 240 volts between the two hot wires.15 A 120V circuit uses one hot wire and the neutral, and a 240V circuit uses both hot wires. Three-phase power usually goes to commercial and industrial buildings, and it has three hot wires.15 Most large industrial motors run on it. Its voltage drop formula uses a √3 multiplier in place of 2.14 It also delivers the same power with less copper than single-phase.

Why does conduit vs. free air matter for wire sizing?

Wire installed in free air can cool itself more easily, so it is allowed to carry more current.11 Wire inside a conduit or raceway traps heat, which lowers its ampacity. The calculator adjusts the ampacity rating based on your selection.

What is derating and when do I need it?

Derating means reducing the ampacity of a wire because of real-world conditions. You need to derate when the ambient temperature is above 30°C (86°F) or when more than three current-carrying conductors share a conduit or cable, or when cables outside a conduit run together without spacing for more than 24 inches (600 mm).6 The Advanced Settings section of this calculator handles both of these factors.

What is power factor?

Power factor is the ratio of true power to apparent power in an AC circuit. A purely resistive load, such as a heater, has a power factor of 1.0. A typical induction motor runs at about 0.85, and lightly loaded motors run lower. Power factor describes AC circuits only, so it does not apply to DC.

How much voltage drop is too much?

An informational note in the NEC says branch circuits sized for no more than 3% voltage drop at the farthest outlet, with no more than 5% total on the feeder and branch circuit, provide reasonable efficiency of operation.4 More than 5% can cause lights to dim, motors to overheat, and sensitive electronics to malfunction.


Sources

  1. Copper Wire Tables (NBS Handbook 100). National Bureau of Standards. 1966;§§ 2.2–2.3. Accessed September 26, 2026.
  2. Aluminum Wire Tables (NBS Handbook 109). National Bureau of Standards. 1972;Conductivity; Size Selection. Accessed September 26, 2026.
  3. 29 CFR 1910.399, Definitions applicable to this subpart. Occupational Safety and Health Administration. "Ampacity". Accessed September 26, 2026.
  4. NFPA 70: National Electrical Code, 2023 Edition. National Fire Protection Association. Section 210.19. Accessed October 9, 2026.
  5. NFPA 70: National Electrical Code, 2023 Edition. National Fire Protection Association. Table 310.4(1). Accessed October 9, 2026.
  6. NFPA 70: National Electrical Code, 2023 Edition. National Fire Protection Association. Section 310.15(B)(1) and Table 310.15(B)(1)(1). Accessed October 9, 2026.
  7. NFPA 70: National Electrical Code, 2023 Edition. National Fire Protection Association. Table 310.15(C)(1). Accessed October 9, 2026.
  8. NFPA 70: National Electrical Code, 2023 Edition. National Fire Protection Association. Article 100, Continuous Load. Accessed October 9, 2026.
  9. NFPA 70: National Electrical Code, 2023 Edition. National Fire Protection Association. Section 240.4(D). Accessed October 9, 2026.
  10. NFPA 70: National Electrical Code, 2023 Edition. National Fire Protection Association. Table 310.16. Accessed October 9, 2026.
  11. NFPA 70: National Electrical Code, 2023 Edition. National Fire Protection Association. Table 310.17. Accessed November 12, 2026.
  12. NFPA 70: National Electrical Code, 2023 Edition. National Fire Protection Association. Chapter 9, Table 8. Accessed November 12, 2026.
  13. NFPA 70: National Electrical Code, 2023 Edition. National Fire Protection Association. Section 110.14(C) and 110.14(C)(1)(a) and (b). Accessed November 12, 2026.
  14. Short-Circuit Current Calculations (Bussmann series): Voltage Drop Calculations. Eaton. 2014;pp. 243 and 244 (How to Figure Volt Loss, Line-to-Neutral, Table A). Accessed November 12, 2026.
  15. Young D. Basic Electricity, Part 10. International Association of Electrical Inspectors (IAEI Magazine). 2006;Figures 2, 4 and 5 (typical service types). Accessed November 12, 2026.
  16. NFPA 70: National Electrical Code, 2023 Edition. National Fire Protection Association. Chapter 9, Table 9 and Note 2. Accessed November 12, 2026.
  17. Repairing Aluminum Wiring (Publication 516). U.S. Consumer Product Safety Commission. 2011;pp. 1 to 4 and 6 to 8. Accessed November 12, 2026.