Engineering calculators

3 Phase Current Calculator

Updated Sep 23, 2026 By Infinity Calculator
Rate Formulas

Input Values

Supply voltage (volts). Choose L-L or L-N beside this field.
Voltage Input Type
L-N is converted internally: VLL = VLN × √3.
1 HP = 745.69987 W. Value is converted to watts before calculating.
PF
Dimensionless, 0.01 – 1.00. Default 0.85 (typical industrial assumption).
Sets the sign convention shown for reactive power Q.
All results are re-rendered in the selected current unit.

Results

Line Current (I)
84.91 A
Apparent Power (S)
58.82 kVA
Reactive Power (Q)
30.99 kVAR
Power per Phase
16.67 kW

Detailed Output

Three-phase balanced-load results for the entered voltage, power and power factor.
Quantity Value Unit

Step-by-Step Solution

Line Current vs. Power Factor

Power Triangle (P, Q, S)

Result Actions


Introduction

The 3 Phase Current Calculator finds the line current in a three-phase electrical system. Enter your voltage, power, and power factor, and it returns the current in amps.

Three-phase power is used in factories, big motors, and large buildings. To pick the right wire size, breaker, or fuse, you need to know the current. Working it out by hand takes time and is easy to get wrong. The calculator runs the same arithmetic every time, so a slipped decimal does not end up in your wire sizing.

It uses the standard formula: I = P ÷ (√3 × V × PF). You can enter voltage as line-to-line or line-to-neutral, and pick units like volts, kilovolts, watts, kilowatts, or horsepower. The results show line current, apparent power (kVA), reactive power (kVAR), power per phase, and the phase angle.

You also get a full step-by-step solution, a table of results, and two charts. One chart shows how current changes with power factor. The other shows the power triangle. Electricians, engineers, and students can follow the worked steps to check their own figures before planning a job.

How to use our 3 Phase Current Calculator

Enter your supply voltage, the load power, and the power factor. The calculator gives you the line current in amps, plus apparent power (kVA), reactive power (kVAR), power per phase, the phase angle, and a full step-by-step solution.

Voltage: Type the supply voltage of your three phase system, like 400 or 480. Then pick the unit next to the box: V, kV, or mV.

Voltage Input Type: Choose Line-to-Line (L-L) if your voltage is measured between two phases. Choose Line-to-Neutral (L-N) if it is measured from one phase to neutral. The tool changes L-N to L-L for you by multiplying by √3.

Power (Real Power, P): Type the real power of the load and pick the unit: W, kW, MW, or HP. Use HP for motors rated in horsepower, and the tool turns it into watts.

Power Factor (PF): Enter a number from 0.01 to 1.00. Use 1.00 for pure resistive loads like heaters. Use about 0.8 to 0.9 for most motors. Check the motor nameplate if you have it.

Load Type: Pick Lagging for inductive loads such as motors and transformers. Pick Leading for capacitive loads. This only sets the plus or minus sign shown for reactive power Q.

Current Output Unit & Precision: Choose how to show the answer: A, kA, or mA. Then choose how many decimal places you want, from 0 to 4.

Press Calculate to see your results, the data table, the charts, and the worked steps. Press Reset to go back to the sample values, or Print Results to save a copy.

What Is Three-Phase Current?

Three-phase power uses three live wires instead of one. Each wire carries the same voltage, but the waves are spaced one-third of a cycle apart. Because the waves take turns peaking, power flows into the load in a smooth, steady stream. That is why factories, shops, farms, and big motors use three-phase power instead of single-phase power.

Three-phase current is the amount of electricity, measured in amps (A), that flows through each line wire of that system. Knowing this number matters because wires, breakers, fuses, and contactors are all picked by amps. Guess too low and the wire overheats. Guess too high and you pay for copper you do not need.

The Formula

For a balanced three-phase load, line current is found with:

I = P ÷ (√3 × VLL × PF)

  • I is the line current in amps
  • P is the real power in watts (1 kW = 1,000 W, 1 HP ≈ 745.7 W)
  • √3 is about 1.732, the three-phase constant
  • VLL is the line-to-line voltage in volts
  • PF is the power factor, a number from 0.01 to 1.00

Line Voltage vs. Phase Voltage

Line-to-line (L-L) voltage is measured between any two hot wires. Line-to-neutral (L-N) voltage is measured from one hot wire to neutral. They are linked by √3: VLL = VLN × 1.732. So a 400 V L-L system has about 230 V L-N, and a 208 V system has about 120 V. Always check which one you are reading before you plug it into the formula.

Why Power Factor Matters

Power factor tells you how much of the current actually does useful work. Motors, welders, and transformers pull extra current to build magnetic fields, so their power factor is below 1. A load at 0.85 PF draws about 18% more current than the same load at 1.00 PF. Lower power factor means more amps, bigger wires, and more heat loss. Most motors run near 0.80 to 0.90, so 0.85 is a common starting guess.

Real, Reactive, and Apparent Power

Three kinds of power show up in AC systems:

  • Real power (P) in watts is the part that does work, like turning a shaft or making heat.
  • Reactive power (Q) in VAR is the part that swings back and forth and does no work.
  • Apparent power (S) in VA is the total the wires must carry, found by S = √3 × VLL × I.

Together they form the power triangle, where S² = P² + Q² and PF = P ÷ S. Inductive loads like motors are called lagging. Capacitor banks are leading and can cancel some lagging VARs to raise power factor.

Wye and Delta Loads

In a wye (star) connection, phase current equals line current. In a delta connection, each phase winding carries line current divided by √3. Total power is the same either way, but the current inside the windings is not, so check the wiring before sizing anything internal.

A Quick Example

A 50 kW load on 400 V three-phase at 0.85 power factor:

I = 50,000 ÷ (1.732 × 400 × 0.85) = 50,000 ÷ 588.9 = 84.91 A

That load needs a breaker and wire rated above 84.91 A, with extra headroom for motor starting, ambient heat, and local code rules.

Good to Know

  • This math assumes a balanced load, meaning all three phases draw the same current.
  • Motors draw 5 to 8 times running current for a few seconds at startup.
  • Long cable runs add voltage drop, which can push current higher than the plain formula shows.
  • Motor nameplates list output horsepower, not input watts, so divide by the motor's efficiency for a true input figure.
  • Always follow the NEC, IEC, or your local wiring rules when picking wire and protection sizes.

Formulas used

Line Current (three-phase)
I = \frac{P}{\sqrt{3} \times V_{LL} \times PF}
Line-to-Line Voltage from Line-to-Neutral
V_{LL} = V_{LN} \times \sqrt{3}
Apparent Power
S = \sqrt{3} \times V_{LL} \times I
Phase Angle
\varphi = \arccos(PF)
Reactive Power
Q = S \sin\varphi
Power per Phase (balanced load)
P_{phase} = \frac{P}{3}
Phase Current in Delta Connection
I_{phase(\Delta)} = \frac{I}{\sqrt{3}}

Frequently asked questions

How many amps does a 10 HP three-phase motor draw at 480V?

About 12 to 14 amps. Here is the math:

  • 10 HP = 7,457 W of output power
  • At 90% efficiency, input power = 7,457 ÷ 0.90 = 8,286 W
  • I = 8,286 ÷ (1.732 × 480 × 0.85) = 11.7 A

Code tables list 14 A for a 10 HP motor at 460V, since they use safe average values. Always use the nameplate amps if you have them.

Why is 1.732 used in three-phase calculations?

1.732 is the square root of 3. It comes from the 120° spacing between the three voltage waves. When you add two phases that are 120° apart, the result is √3 times one phase, not 2 times.

That is why line-to-line voltage is √3 × line-to-neutral voltage, and why √3 shows up in every three-phase power and current formula.

How do you convert kVA to amps in a three-phase system?

Use this formula:

I = (kVA × 1,000) ÷ (1.732 × VLL)

Example: a 100 kVA transformer at 480V gives I = 100,000 ÷ (1.732 × 480) = 120 A.

Power factor is not used here. kVA is already the total the wires must carry.

How do you convert three-phase amps back to kW?

Flip the current formula around:

kW = (1.732 × VLL × I × PF) ÷ 1,000

Example: 85 A at 400V and 0.85 PF gives (1.732 × 400 × 85 × 0.85) ÷ 1,000 = 50 kW.

Skip the PF and you get kVA instead of kW.

Why does a three-phase load draw less current than a single-phase load of the same size?

Because the power is shared across three wires instead of one. For the same voltage and power, three-phase current is about 42% lower.

  • Single-phase: I = P ÷ (V × PF)
  • Three-phase: I = P ÷ (1.732 × V × PF)

Lower current means smaller wires, less heat, and cheaper installs. That is the main reason big loads use three-phase.

What power factor should I use if I don't know the load's power factor?

Use these common starting values:

  • 1.00 for heaters, ovens, and resistive loads
  • 0.85 for general motor loads and mixed shop loads
  • 0.80 for small or lightly loaded motors
  • 0.95 or higher for drives and modern LED lighting

These are guesses. The motor or equipment nameplate gives the real number, and a power meter gives the true value under load.

Does the neutral wire carry current in a three-phase system?

In a perfectly balanced load, the three currents cancel and the neutral carries almost nothing.

But real systems are rarely perfect. Neutral current shows up when:

  • The three phases carry different loads
  • You have many single-phase loads on one phase
  • Computers, LED drivers, and other electronics create harmonics

Harmonic current can add up in the neutral and make it hotter than the line wires, so never undersize it in a building with lots of electronics.

How do you find the current in an unbalanced three-phase system?

The √3 formula only works for balanced loads. For unbalanced loads, work out each phase on its own:

Iphase = Pphase ÷ (VLN × PF)

Do this for phase A, B, and C using each one's own power and voltage. Then size your wires and breaker for the highest phase current, not the average.

What size breaker do you need for a three-phase load?

For a continuous load, a common rule is breaker size = load current × 1.25, then round up to the next standard breaker.

Example: an 85 A load × 1.25 = 106 A, so you would use a 110 A or 125 A breaker.

Motors are different. Their starting current is 5 to 8 times running current, so motor circuits use special sizing rules for the breaker and separate overload protection. Check the NEC, IEC, or your local code.

How do you measure three-phase current with a clamp meter?

Clamp around one conductor at a time. Read L1, then L2, then L3 and write down each value.

If you clamp two or three wires at once, the currents cancel and you get a reading near zero. Compare the three readings: if one is far off from the others, your load is unbalanced or something is wrong.

What happens to the current if one phase is lost?

This is called single phasing, and it is hard on motors. The motor keeps spinning but the two remaining wires must carry all the load. Their current jumps to roughly 1.7 to 2 times normal.

The windings overheat fast and can burn out in minutes. This is why motors need phase-loss protection or proper overload relays.

Do you need to include motor efficiency when calculating current?

Yes. A motor nameplate lists horsepower as output power at the shaft, not the power it pulls from the line. The motor also burns some power as heat.

Divide output watts by efficiency to get input watts:

Input W = (HP × 745.7) ÷ efficiency

A 20 HP motor at 91% efficiency pulls 14,914 ÷ 0.91 = 16,389 W. Skip this step and your current will come out about 10% too low.