Engineering calculators

3 Phase Power Calculator

Updated Jun 2, 2026 By Jehan Wadia
# 3 Phase Power Calculator Module
Inputs
Line-to-Neutral is converted: V_LL = V_LN × √3.
Enter a voltage of at least 1.
Enter a current of at least 1.
Power factor must be between 0.01 and 1.0.
Quantity must be at least 1.
Results
Apparent Power (VA)
Apparent Power (kVA)
Active Power (W)
Active Power (kW)
Reactive Power (kVAR)
Power Angle (Φ)
Power Triangle
Summary
QuantityValue

Introduction

This 3 Phase Power Calculator helps you quickly find active power (kW), apparent power (kVA), reactive power (kVAR), current, and voltage in three-phase and single-phase electrical systems. Whether you are an electrician, engineer, or student, this tool makes complex power calculations simple. Just enter your known values, and the calculator does the rest.

The calculator has three modes. In the first mode, you enter voltage, current, and power factor to find all power values. In the second mode, you enter power and voltage to find current. In the third mode, you enter power and current to find voltage. Each mode supports both line-to-line and line-to-neutral voltage, and you can switch between three-phase and single-phase with one click.

All results update instantly and include a power triangle chart so you can see how active, reactive, and apparent power relate to each other. A summary table is also shown below the chart for easy reference. This tool uses standard electrical formulas, including S = √3 × V_LL × I for three-phase apparent power and P = S × cosΦ for active power.

How to Use Our 3 Phase Power Calculator

Enter your electrical values below to calculate power, current, or voltage for three-phase and single-phase systems. The calculator gives you apparent power (kVA), active power (kW), reactive power (kVAR), power factor, and power angle.

Step 1: Pick a Calculation Mode. Use the tabs at the top to choose what you want to find. "Power from V, I, PF" finds power when you know voltage, current, and power factor. "Current from Power" finds current when you know power and voltage. "Voltage from Power" finds voltage when you know power and current.

Step 2: Select the Phase Type. Click "Three-Phase" for three-phase systems or "Single-Phase" for single-phase systems. This changes the formula used in the calculation.

Step 3: Choose the Voltage Type. Pick "Line-to-Line" if your voltage is measured between two phases. Pick "Line-to-Neutral" if it is measured from one phase to neutral. The calculator converts between them using √3.

Step 4: Enter the Voltage. Type the voltage in volts (V). This must be at least 1 volt. If you need to verify voltage relationships in your circuit, our Voltage Divider Calculator can help with resistive networks.

Step 5: Enter the Current. Type the current in amps (A). This must be at least 1 amp. This field appears in Mode 1 and Mode 3. You can also use our kVA to Amps Calculator to convert between power and current values.

Step 6: Enter the Power Factor (cosΦ). Type a number between 0.01 and 1.0. A power factor of 1 means all power is active. Most real loads have a power factor between 0.8 and 0.95.

Step 7: Enter the Quantity. In Mode 1, type how many identical loads you have. The calculator multiplies the result by this number. Set it to 1 for a single load.

Step 8: Enter Apparent Power (kVA) or Active Power (kW). In Mode 2 and Mode 3, type the known power values in kilowatts or kilovolt-amps.

Step 9: Click "Calculate." The results show up right away, along with a bar chart of the power triangle and a summary table. Click "Reset" to go back to the default values.

What Is 3 Phase Power?

3 phase power is a way of sending electricity using three separate wires, each carrying current that peaks at a different time. This system is used in factories, large buildings, and heavy machines because it delivers more power in a smoother, steadier way than single-phase power. Most homes use single-phase power, but the electrical grid itself runs on three phases.

How 3 Phase Power Works

In a 3 phase system, three alternating currents flow through three wires. Each current is offset by 120 degrees from the others. This means power is always being delivered on at least one wire at any moment, which keeps motors and equipment running smoothly without the pulsing effect you get with single-phase power.

Key Terms You Should Know

  • Apparent Power (kVA) — The total power flowing through a circuit, including both useful and wasted portions. It is measured in kilovolt-amps.
  • Active Power (kW) — The real power that does actual work, like turning a motor or producing heat. It is measured in kilowatts. For general physics power problems, see our Power Calculator.
  • Reactive Power (kVAR) — Power that bounces back and forth between the source and the load. It does no useful work but is needed to maintain magnetic fields in motors and transformers.
  • Power Factor (cosΦ) — A number between 0 and 1 that tells you how much of the apparent power is being used as active power. A power factor of 1.0 means all the power is doing useful work. Most real systems have a power factor between 0.8 and 0.95.
  • Line-to-Line Voltage (V_LL) — The voltage measured between any two of the three phase wires.
  • Line-to-Neutral Voltage (V_LN) — The voltage measured between one phase wire and the neutral wire. It equals V_LL divided by √3 (about 1.732).

Basic 3 Phase Power Formulas

The main formula for three-phase apparent power is: S = √3 × V_LL × I, where S is apparent power in volt-amps, V_LL is line-to-line voltage, and I is current in amps. To find active power, multiply by the power factor: P = √3 × V_LL × I × cosΦ. For single-phase circuits, the formula simplifies to S = V × I since there is no √3 factor. You can explore the fundamental relationship between voltage, current, and resistance using our Ohms Law Calculator, or convert between watts and amps with our Watts To Amps Calculator and Amps to Watts Calculator.

Why Power Factor Matters

A low power factor means your system draws more current than it needs to do the same amount of work. This wastes energy, increases electricity bills, and puts extra stress on wires and equipment. Utilities often charge penalties for a low power factor. You can improve it by adding capacitor banks or using power factor correction devices. To understand how capacitors behave in your circuits, try our Capacitor Calculator. If you want to estimate how power factor and load affect your energy costs, our Electricity Cost Calculator can help.

When to Use This Calculator

Use this calculator when you need to find the power, current, or voltage in a three-phase or single-phase electrical system. It is helpful for sizing circuit breakers, selecting cables, checking transformer loads, and estimating energy costs. When selecting wire and cable sizes for your installation, our Wire Size Calculator and Voltage Drop Calculator are valuable companions. For conduit planning, check out the Conduit Fill Calculator. If you are sizing a backup power source, our Generator Sizing Calculator pairs well with this tool. Electricians working with resistor networks may also find the Parallel Resistor Calculator and Impedance Calculator useful. Electricians, engineers, and students can all use it to solve common power system problems quickly.


Frequently asked questions

What is the difference between line-to-line and line-to-neutral voltage?

Line-to-line voltage is measured between two phase wires. Line-to-neutral voltage is measured from one phase wire to the neutral wire. Line-to-line voltage is always higher. To convert, multiply line-to-neutral voltage by √3 (about 1.732). For example, if your line-to-neutral voltage is 230 V, the line-to-line voltage is about 400 V.

Why does the calculator show reactive power as zero when my power factor is 1?

A power factor of 1 means all the power in your circuit is active power doing useful work. There is no reactive power bouncing back and forth. So the calculator correctly shows 0 kVAR. This happens with purely resistive loads like heaters and incandescent lights.

Can I use this calculator for DC circuits?

No. This calculator is made for AC circuits only. DC circuits do not have a power factor, reactive power, or phase angle. For DC, power is simply voltage times current (P = V × I). The √3 factor and power triangle only apply to AC systems.

What does the quantity field do in Mode 1?

The quantity field lets you multiply the result by the number of identical loads you have. For example, if you have 5 identical motors, set the quantity to 5. The calculator will give you the total combined power for all 5 motors instead of just one.

Why is my current from kVA different from my current from kW in Mode 2?

Current from kVA is based on total apparent power, which includes both active and reactive power. Current from kW is based only on active power. Since active power is always less than or equal to apparent power, the current from kW will be less than or equal to the current from kVA. The difference depends on the power factor.

What power factor should I use if I do not know it?

If you do not know the exact power factor, use 0.85 as a general estimate. Most industrial and commercial loads fall between 0.80 and 0.95. Motors typically have a power factor around 0.85. Resistive loads like heaters are close to 1.0. Check the nameplate on your equipment for the exact value.

What is the power triangle shown in the chart?

The power triangle is a bar chart that shows three types of power side by side. Active power (kW) is the real power doing work. Reactive power (kVAR) is the power stored and released by magnetic fields. Apparent power (kVA) is the total combination of both. Apparent power is always the largest of the three.

How do I switch between three-phase and single-phase?

Click the "Three-Phase" or "Single-Phase" button in the Phase Type section of any mode. When you pick single-phase, the calculator removes the √3 factor from the formula. The results update right away when you switch.

What is the power angle shown in the results?

The power angle (Φ) is the angle between active power and apparent power. It comes from the power factor using the formula Φ = arccos(PF). A power angle of 0° means all power is active. A larger angle means more reactive power is present. For example, a power factor of 0.85 gives a power angle of about 31.79°.

Why does Mode 3 need a power factor but Mode 2 does not?

Mode 2 calculates the power factor for you from the kVA and kW values you enter (PF = kW ÷ kVA). Mode 3 only has apparent power and current as inputs, so it cannot figure out the power factor on its own. You must enter it so the calculator can split apparent power into active and reactive parts.

What units does this calculator use?

Voltage is in volts (V). Current is in amps (A). Apparent power is in volt-amps (VA) or kilovolt-amps (kVA). Active power is in watts (W) or kilowatts (kW). Reactive power is in kilovolt-amps reactive (kVAR). The power angle is in degrees (°).

Can kW ever be larger than kVA?

No. Active power (kW) can never be larger than apparent power (kVA). The power factor is always between 0 and 1, and kW = kVA × power factor. If you enter kW greater than kVA in Mode 2, the calculator will cap the power factor at 1.0.

Does this calculator account for efficiency losses?

No. This calculator gives you the electrical power values at the point of measurement. It does not include motor efficiency, cable losses, or transformer losses. To find the actual power consumed by a device, you would need to divide the output power by the efficiency rating of the equipment.