Engineering calculators

kVA Calculator

Updated Nov 12, 2026 By Infinity Calculator Formulas Sources
Rate
Voltage, Current & kVA
Phase
V
The RMS voltage supplied to the circuit, in volts. For three-phase, use the line-to-line voltage, such as 208 V or 480 V.
A
The current flowing through the circuit, in amperes. For three-phase, use the current in one line.
kVA
Apparent power. Leave one of the three fields blank to solve for it.

Result

Step-by-Step Solution

Visualization


Introduction

This kVA calculator helps you find apparent power in an electrical circuit. kVA stands for kilovolt-amperes, and it measures apparent power, the total power delivered to a device or system.1 Unlike kilowatts (kW), which only count the real power that does useful work, kVA includes both real power and reactive power.1 Knowing your kVA rating is important when you size generators, transformers, wiring, and other electrical equipment.

The calculator has two modes. In the first mode, you enter voltage and current to calculate kVA, or leave any one of the three fields blank to solve for it. This mode works for both single-phase and three-phase systems. In the second mode, you use kW and power factor to find kVA, or solve for any missing value in that group. Each calculation gives you a step-by-step solution and a chart so you can see how the values relate to each other.

How to Use Our kVA Calculator

Enter any two known values in a tab and leave the third field blank. The calculator will solve for the missing value and show the answer, a step-by-step solution, and a chart.

Voltage, Current & kVA Mode

Phase: Pick either Single-Phase or Three-Phase. This tells the calculator which formula to use. Three-phase systems multiply by 1.7321 (√3).

Voltage (V): Enter the RMS voltage of your circuit in volts. This is the electrical pressure that pushes current through the system. For a three-phase circuit, enter the line-to-line voltage, measured between two of the three lines, which is how service and motor voltages are quoted.3

Current (A): Enter the current flowing through the circuit in amps. This is how much electricity the load draws. For a three-phase circuit, enter the line current, the current in one of the three lines.1

kVA: Enter the apparent power in kilovolt-amperes. Leave this field blank if you want the calculator to find it from the voltage and current you entered.

kW, Power Factor & kVA Mode

Real Power (kW): Enter the active power your load uses in kilowatts. This is the actual work the electricity does.

Power Factor (PF): Enter a number between 0.01 and 1.00. Power factor shows how much of the apparent power is doing real work.1 A value of 1.00 means all of it is real power.1 A lower number means the wires carry extra current for the same real power.3

Apparent Power (kVA): Enter the total apparent power in kilovolt-amperes. Leave this field blank if you want the calculator to find it from the kW and power factor you entered.

What Is kVA?

kVA stands for kilovolt-ampere. It is a unit that measures apparent power in an electrical circuit.1 Apparent power is the total power that flows through wires to a device or load.1 It includes both the real power that does useful work and the reactive power that flows back to the source.1

How kVA Is Calculated

There are two main ways to find kVA. The first uses voltage and current. For a single-phase circuit, you multiply volts by amps and divide by 1,000.1 For a three-phase circuit, you also multiply by √3 before dividing by 1,000.1 √3, the square root of 3, is about 1.7321. The second way uses real power (kW) and power factor. You divide kW by the power factor to get kVA.1 Multiplying volts by amps comes from the power equation for DC circuits (power equals current times voltage), which is usually taught alongside Ohm's Law, the rule that links voltage, current, and resistance. In an AC circuit, volts times amps gives the apparent power in volt-amperes, which is why the result is in kVA rather than kW.

Single-Phase Formula

kVA = (Volts × Amps) ÷ 1,0001

Three-Phase Formula

kVA = (Volts × Amps × √3) ÷ 1,0001

Power Factor Formula

kVA = kW ÷ Power Factor1

kVA vs. kW

kW (kilowatts) measures real power: the power that actually does work, like spinning a motor or lighting a bulb.1 kVA measures apparent power, the full amount of power drawn from the source.1 The difference between them is caused by reactive power, which moves back and forth in the circuit without doing useful work.1 Reactive power is closely related to impedance in the circuit.1 The power factor tells you how much of the apparent power is real power.1 A power factor of 1.0 means all the power is doing useful work, so kVA equals kW.1 A lower power factor means more current for the same real power.3

Why kVA Matters

Generators carry a capacity rating in kVA on their nameplates.1 Transformers are rated in kVA too.2 So are many UPS systems. Their wiring and components must handle the full apparent power, not just the real power.3 If you only look at kW and ignore kVA, you could overload your equipment. Knowing the correct kVA helps you pick the right size generator or transformer for your needs and keeps your electrical system safe and efficient.


Formulas used

Single-Phase Apparent Power (kVA) 1
\text{kVA} = \frac{V \times I}{1000}
Three-Phase Apparent Power (kVA) 1
\text{kVA} = \frac{V \times I \times \sqrt{3}}{1000}
Apparent Power from Real Power and Power Factor 1
\text{kVA} = \frac{\text{kW}}{\text{PF}}
Real Power from Apparent Power and Power Factor 1
\text{kW} = \text{kVA} \times \text{PF}
Power Factor from Real and Apparent Power 1
\text{PF} = \frac{\text{kW}}{\text{kVA}}
Reactive Power (kVAR) 5
\text{kVAR} = \sqrt{\text{kVA}^2 - \text{kW}^2}

Frequently asked questions

What does kVA stand for?

kVA stands for kilovolt-ampere. It is a unit of apparent power in an electrical system.1 One kVA equals 1,000 volt-amperes. It tells you the total power flowing through a circuit, including both real power and reactive power.1

When should I use single-phase vs. three-phase?

Use single-phase for most homes and small loads, since homes usually have single-phase power.4 A 120 V load runs on one hot wire and the neutral.2 Use three-phase for systems with three hot wires.3 Three-phase power is used widely in industry.4 Larger motors usually require it.3 If you are not sure, check the nameplate on your equipment or your electrical panel.

Why does the three-phase formula multiply by 1.7321?

The number 1.7321 is the square root of 3 (√3). In a three-phase system, three separate voltage waves are spaced 120° apart.1 Multiplying by √3 accounts for how these three waves combine to deliver more total power than a single phase at the same voltage and current.1

What is power factor?

Power factor is a number between 0 and 1 that shows how much of the apparent power is doing real work.1 A power factor of 1.0 means all the power is useful.1 A power factor of 0.8 means only 80% of the apparent power does real work. The rest of the apparent power is reactive power, which flows back and forth without doing useful work.1 At a power factor of 0.8, reactive power is 60% of the apparent power, because real, reactive and apparent power form a right triangle rather than adding up.

What is a typical power factor for common loads?

Resistive loads like heaters and incandescent lights have a power factor close to 1.0.6 Motors usually range from 0.8 to 1.7 A motor's power factor drops when it runs below about 50% of full load.3 U.S. rules require most fluorescent lamp ballasts made since November 14, 2014 to have a power factor of at least 0.9, or at least 0.5 for residential ballasts.10 A computer with an internal power supply rated 75 watts or more needs a power factor of at least 0.90 at 50% load to earn ENERGY STAR.11

Can kVA ever equal kW?

Yes. When the power factor is exactly 1.0, kVA equals kW.1 This means all the apparent power is real power and there is no reactive power.6 Purely resistive loads like electric heaters come close to this.6

Why is my kVA higher than my kW?

kVA is always equal to or greater than kW.1 The difference comes from reactive power.1 Reactive power does not do useful work, but it still flows through the wires.3 A lower power factor means a bigger gap between kVA and kW.

What voltage value should I enter?

Enter the RMS voltage of your circuit. For most U.S. homes this is 120 V or 240 V.2 For a three-phase circuit, enter the line-to-line voltage, measured between two of the three lines.3 Most three-phase distribution transformers supply 208Y/120 V or 480Y/277 V.8 In each pair the larger number is the line-to-line voltage, because line-to-line readings are 1.73 times line-to-neutral readings.3 So for a three-phase kVA figure, use 208 V or 480 V, not 120 V or 277 V. Check your panel or equipment nameplate for the exact number.

How do I size a generator using kVA?

Add up the kVA of all the loads you plan to run at the same time. Then pick a generator rated at or above that total. A generator's nameplate gives its capacity in both kVA and kW at a specified power factor.1 The total kW of the loads must fit within the kW rating too. Motors typically need four times the power to start as they do to run, so the generator must be big enough to start the largest motor.9

How do I convert kVA to amps?

For single-phase: Amps = (kVA × 1,000) ÷ Volts.1 For three-phase: Amps = (kVA × 1,000) ÷ (Volts × √3).1 You can use this calculator to do it. Enter the kVA and voltage, leave the current field blank, and press Calculate.

How do I convert amps to kVA?

For single-phase: kVA = (Volts × Amps) ÷ 1,000.1 For three-phase: kVA = (Volts × Amps × √3) ÷ 1,000.1 Enter the voltage and current in this calculator, leave the kVA field blank, and press Calculate.

What is reactive power (kVAR)?

kVAR stands for kilovolt-ampere reactive. It is the part of apparent power that does not do useful work.1 It flows back and forth between the source and loads like motors and transformers.1 The power triangle links all three: kVA² = kW² + kVAR².5 The chart in Tab 2 of this calculator shows all three values side by side.


Sources

  1. DOE Fundamentals Handbook: Electrical Science, Volume 3 of 4 (DOE-HDBK-1011/3-92). U.S. Department of Energy. 1992;Module ES-09, pp. 2-4, 17, 20-21; Module ES-10, p. 9. Accessed September 27, 2026.
  2. DOE Fundamentals Handbook: Electrical Science, Volume 4 of 4 (DOE-HDBK-1011/4-92). U.S. Department of Energy. 1992;Module ES-13, p. 13; Module ES-15, pp. 23-24. Accessed September 27, 2026.
  3. Determining Electric Motor Load and Efficiency (DOE/GO-10097-517). U.S. Department of Energy. p. 10, Electrical Glossary. Accessed September 27, 2026.
  4. Improving Motor and Drive System Performance: A Sourcebook for Industry (DOE/GO-102014-4356). U.S. Department of Energy. 2014;p. 5. Accessed September 27, 2026.
  5. Kuphaldt TR. Electric Circuits II - Alternating Current, Section 11.2: True, Reactive, and Apparent Power. LibreTexts. The Power Triangle. Accessed September 27, 2026.
  6. Kuphaldt TR. Electric Circuits II - Alternating Current, Section 11.3: Calculating Power Factor. LibreTexts. Accessed September 27, 2026.
  7. Improving Fan System Performance: A Sourcebook for Industry (DOE/GO-102003-1294). U.S. Department of Energy. 2003;p. 34. Accessed September 27, 2026.
  8. Energy Conservation Program: Energy Conservation Standards for Distribution Transformers (final rule). Federal Register. U.S. Department of Energy. 2024;89 FR 29871 and 29881. Accessed November 12, 2026.
  9. Standby Electric Generators. NDSU Agriculture, North Dakota State University. Selecting the Right Generator. Accessed November 12, 2026.
  10. 10 CFR 430.32 Energy and water conservation standards and their compliance dates. Electronic Code of Federal Regulations. 430.32(m)(1) and (m)(3), fluorescent lamp ballasts. Accessed November 12, 2026.
  11. ENERGY STAR Program Requirements for Computers, Version 9.0. U.S. Environmental Protection Agency (ENERGY STAR). 2025;section 3.2.2, Tables 1 and 2. Accessed November 12, 2026.